2.1
Monitoring Requirement
In
accordance with the approved EM&A Manuals, 24-hour Total Suspended
Particulates (TSP) level at the designated air quality monitoring station is
required. Impact 24-hour TSP monitoring should be carried out at least once
every 6 days. In case of complaints, 1-hour TSP monitoring should be carried
out at least 3 times per 6 days when the highest dust impacts are likely to
occur. The Action and Limit Levels of the air quality monitoring are given in Appendix
C.
2.2
Monitoring Equipment
The
24-hour TSP air quality monitoring was performed using High Volume Air Samplers
(HVS) located at each of the designated monitoring station. Portable TSP
Monitors would be used in case of complaints for 1-hour TSP monitoring.
Table 2.1 summarizes the equipment used in air
quality monitoring.
Table 2.1 Air
Quality Monitoring Equipment
Item |
Brand |
Model |
Equipment |
Serial Number |
1 |
Tisch |
TE-5170 (TSP) |
High Volume
Sampler |
|
TE-300-310X |
- Mass Flow
Controller |
2037 |
||
TE-5005X |
- Blower
Motor Assembly |
3482 |
||
TE-5007X |
- Mechanical
Timer |
4488 |
||
TE-5009X |
- Continuous
Flow Recorder |
4371 |
||
2 |
Tisch |
TE-5170 (TSP) |
High Volume
Sampler |
|
TE-300-310X |
- Mass Flow
Controller |
2524 |
||
TE-5005X |
- Blower
Motor Assembly |
4037 |
||
TE-5007X |
- Mechanical
Timer |
5160 |
||
TE-5009X |
- Continuous
Flow Recorder |
4377 |
||
3 |
Tisch |
TE-5170 (TSP) |
High Volume
Sampler |
|
TE-300-310X |
- Mass Flow
Controller |
2618 |
||
TE-5005X |
- Blower
Motor Assembly |
3838 |
||
G3031 |
- Mechanical
Timer |
2251 |
||
G1051 |
- Continuous
Flow Recorder |
2307 |
||
4 |
Tisch |
TE-5025A |
HVS Sampler Calibrator |
438320/2456 |
5 |
*Sibata |
Model
LD-3B |
Sibata Portable
TSP Monitors |
NA |
Note:
No complaint of air quality was received. Therefore,
no impact 1-hour TSP monitoring was conducted.
2.3
Monitoring Methodology
2.3.1
24-hour TSP air quality monitoring
HVS Installation
The following
guidelines were adopted during the installation of HVS:
n Sufficient support is
provided to secure the samplers against gusty wind.
n No two samplers are
placed less than 2 meters apart.
n The distance between
the sampler and an obstacle, such as buildings, is at least twice the height
that the obstacle protrudes above the sampler.
n
A
minimum of 2 meters of separation from walls, parapets and penthouses is
required for rooftop samples.
n
A
minimum of 2 meters separation from any supporting structure, measured
horizontally is required.
n
No
furnaces or incineration flues are nearby.
n
Airflow
around the samplers is unrestricted.
n
The
samplers are more than 20 meters from the drip line.
n
Any
wire fence and gate, to protect the sampler, should not cause any obstruction
during monitoring.
Filters Preparation
Fiberglass filters (provided
by the HOKLAS accredited laboratory) shall be used (Note: these filters have a
collection efficiency of larger than 99% for particles of 0.3 µm diameter). A
HOKLAS accredited laboratory (ALS Technichem (HK) Pty
Ltd.) is responsible for the preparation of 24-hr conditioned and pre-weighed
filter papers for monitoring team.
All filters are
equilibrated in the conditioning environment for 24 hours before weighing. The
conditioning environment temperature is around 25°C and not variable by more
than ±3°C; the relative humidity (RH) is < 50% and not variable by more than
±5%. A convenient working RH is 40%.
Operating
/ Analytical Procedures
Operating / analytical
procedures for the air quality monitoring are highlighted as follows:
n Prior to the
commencement of the dust sampling, the flow rate of the HVS are properly set
(between 0.6 m3/min and 1.7 m3/min) in accordance with the
EM&A manual. The flow rate shall be indicated on the flow rate chart.
n The power supply shall
be checked to ensure the samplers worked properly.
n On sampling, the
samplers shall be operated for 5 minutes to establish thermal equilibrium
before placing any filter media at the designated air quality monitoring
station.
n The filter holding
frame is then removed by loosening the four nuts and carefully a weighted and
conditioned filter is centered with the stamped number upwards, on a supporting
screen.
n The filter shall be
aligned on the screen so that the gasket formed an airtight seal on the outer
edges of the filter. Then the filter holding frame is tightened to the filter
holder with swing bolts. The applied pressure should be sufficient to avoid air
leakage at the edges.
n The shelter lid shall
be closed and secured with the aluminum strip.
n The timer is then
programmed. Information shall be recorded on the record sheet, which included
the starting time, the weather condition and the filter number (the initial
weight of the filter paper can be found out by using the filter number).
n After sampling, the
filter shall be removed and sent to laboratory for weighing. The elapsed time
is also recorded.
n Before weighing, all
filters are equilibrated in a conditioning environment for 24 hours. The
conditioning environment temperature should be between 25°C and 30°C and not
vary by more than ±3°C; the relative humidity (RH) should be < 50% and not
vary by more than ±5%. A convenient working RH is 40%. Weighing results are
returned to MCL for further analysis of TSP concentrations collected by each
filter.
2.3.2
1-hour TSP air quality monitoring
Operating
/ Analytical Procedures
The measuring procedures of the 1-hr dust meter
are in accordance with the Manufacturer’s instruction Manual as follows:
§ Pull up the air sampling inlet cover
§ Change the Mode 0 to BG once
§ Push Start/Stop switch once
§ Turn the knob to SENSI.ADJ and press it
§ Push Start/Stop switch once
§ Return the knob to the position MEASURE slowly
§ Push the timer set switch to set measuring time
§ Remove the cap and make a measurement
2.4
Maintenance /
Calibration
2.4.1 24-hour TSP air quality monitoring
The following maintenance
/ calibration are required for the HVS:
n The high volume motors
and their accessories are properly maintained. Appropriate maintenance such as
routine motor brushes replacement and electrical wiring checking are made to
ensure that the equipments and necessary power supply
are in good working condition.
n All HVS shall be
calibrated (five point calibration) using Calibration Kit upon installation and
thereafter in every 3 months.
n A copy of the
calibration certificates for the HVS and calibrator are provided in
2.4.2 1-hour TSP air quality monitoring
The portable TSP
monitor should be calibrated at 1 year intervals
2.5.1
According
to the EM&A Manual, three air quality monitoring locations, namely KTD1,
KTD2 and KER1, are covered by this Contract within the South Apron Area of
Former Kai Tak Airport. The other two air quality
monitoring locations, which are identified in Cha Kwo
Ling area, are farther than 500m away from the site boundary and thus not
covered by this Contract. The monitoring works in Cha Kwo
Ling area are covered by other Contract(s) respectively.
2.5.2
According
to the approved alternative baseline air quality and noise monitoring locations
(EPD reference: EP2/K19/A/21 Pt.5), the original monitoring locations (KTD1,
KTD2 and KER1) are proposed to be replaced by alternative monitoring locations
(KTD1a, KTD2a and KER1b) for air quality monitoring, they are summarized in Table 2.2
and shown in Figure
2.
Table 2.2 Location
of Air Quality Monitoring Station
Monitoring
Station |
Location |
KTD1a |
Centre of Excellence in Paediatrics
(Children’s Hospital) |
KTD2a |
G/IC Zone next to Kwun Tong
Bypass (Future Hospital at Site 3C1) |
KER1b |
Site Boundary at Cheung Yip Street |
2.6.1 The schedule of air quality monitoring in reporting month is provided in Appendix E.
2.6.2 No Action / Limit Level exceedance was
recorded for 24-hr TSP at KTD1a, KTD2a and KER1b in the reporting month.
2.6.3 No complaint of air quality was received. Therefore, no impact 1-hour TSP
monitoring was conducted in the reporting month.
2.6.4 During the reporting month, major dust sources including loading and
unloading of C&D wastes, vehicles movement were observed in the site. Non-project
related construction activities at the nearby construction site and road
traffic along Shing Cheong Road, Cheung Yip Street
and the Kwun Tong By-pass were observed. The above factors
may affect the monitoring results.
2.6.5 The weather conditions during the monitoring are provided in Appendix K.
2.6.6 The monitoring data of 24-hr TSP are summarized in Table 2.3. Detailed monitoring data are
presented in Appendix F.
Table
2.3 Summary of 24-hr TSP Monitoring Results
Parameter |
Monitoring
Station |
Average
(µg/m3) |
Range
(µg/ m3) |
Action
Level (µg/ m3) |
Limit
Level (µg/ m3) |
24-hr TSP in µg/m3 |
KTD1a |
114 |
32 - 167 |
177 |
260 |
KTD2a |
75 |
60 - 89 |
157 |
||
KER1b |
60 |
37 - 90 |
172 |
2.6.7 The Event and Action Plan for air quality is given in Appendix H.
2.7
Comparison of 24-hr
TSP Monitoring Results with EIA Predictions
2.7.1 The monitoring data of 24-hr TSP was compared with the EIA predictions as
summarized in Table 2.4.
Table
2.4 Comparison
of 24-hr TSP data with EIA predictions
Monitoring
Station |
Receiver
Reference |
Predicted
Maximum 24-hour TSP Concentration (µg/m3) |
24-hour
TSP concentration in January 2018 (µg/m3) |
Average
24-hour TSP concentration in January
2018 (µg/m3) |
KTD1a |
KTD3 |
126 |
32 - 167 |
114 |
KTD2a |
- |
- |
60 - 89 |
75 |
KER1b |
KTD6 |
169 |
37 - 90 |
60 |
Note:
For
KTD2a, there was no receiver reference in the EIA report, EIAR-174/2013.
Predicted
Maximum TSP Concentration extracted from Table 4.14 of EIA Report, EIAR-174/2013.
2.7.2
The 24-hour TSP
monitoring results at KER1b was below the Predicted Maximum 24-hr TSP concentration in the approved Environmental
Impact Assessment (EIA) Report and no Action / Limit Level exceedance was
recorded in the reporting period.
2.7.3
The 24-hour TSP monitoring result of KTD1a on 3 and 26 January 2018
exceeded the prediction in the approved EIA report. No project related dust
source was observed during the site monitoring. The discrepancy between the
24-hour TSP concentration and EIA Prediction in KTD1a is considered due to dust
source from the non-project related construction activities near the monitoring
station and the road travel along Shing Fung Road.